Intermediate circuit heat exchanger
VVER-1200 power unit, 2024
Ø 1,000 × 7,666 mm1.2 MPa, 95 °C08Х18Н10Т
Removes heat from the intermediate cooling circuit to service water.
- Working pressure
- 1.2 MPa
- Working temperature
- 95 °C
- Inner diameter
- 1,000 mm
- Working medium
- water
Task
Heat from the intermediate circuit must go to service water so that a leaking tube never lets river water into the clean circuit.
The bureau’s solution
The intermediate circuit runs in the shell at the higher pressure and service water in the tubes, so a leak flows out of the clean circuit, not into it. Tubes are cleaned from the channel side.
What the bureau did
- design documents
- manufacture
- tests
Operating conditions
- Design pressure
- 1.6 MPa
- Working pressure
- 1.2 MPa
- Design wall temperature
- 120 °C
- Working temperature
- 95 °C
- Working medium
- water
- Safety class by NP-001-15
- 3НAssigned by the plant designer and stated in the specification
- Rules
- NP-089-15, NP-104-18, NP-105-18
Design
- Type
- Shell-and-tube heat exchanger
- Inner diameter
- 1,000 mm
- Shell length
- 6,000 mm
- Wall thickness
- 8 mmBy GOST 34233.2: sₚ = p·D / (2·φ·[σ] − p) = 1.6·1,000 / (2·1·152.5 − 1.6) = 5.3 mm. With a 1 mm allowance, 8 mm plate was taken. [σ] = 152.5 MPa for 08Х18Н10Т at 120 °C — GOST 34233.1, table A.3.
- Shell material
- 08Х18Н10Т
- Overall size
- 7,666 × 1,236 × 1,576 mm
- Empty mass
- 9,180 kg
Tests and inspection
- Hydraulic test pressure
- 2.25 MPa1.25 · p · [σ]₂₀ / [σ]ₜ = 1.25 · 1.6 · 168 / 152.5 — GOST 34347, 7.11.3
- Non-destructive testing
- Visual and dimensional, liquid penetrant; 100 % radiography of shell butt welds
Product documents
- Passport
- Open for print
- Strength calculation
- in the delivery set
- Operating manual
- in the delivery set
- Metal certificates
- in the delivery set
Lead time
36 weeks from signed specification to shipment